1500kVAR Avtron Reactive Load K841B D38355 | 480V, 3PH, 60Hz

Avtron Reactive Load Bank


  • Used
  • Avtron K841B D38355
  • Reactive Load Bank
  • 1500kVAR
  • 480V
  • 3PH
  • 60Hz
  • Load Steps: 375kVAR, 375kVAR, 375kVAR, 187.5kVAR, 75kVAR, 75kVAR, 37.5kVAR
  • S/N: 119
  • Made In U.S.A.


The Avtron K841B reactive load bank is designed for use with a resistive load bank to test a generator or power source at 0.8 power factor (lagging). To achieve a 0.8 power factor, the reactive load bank should be sized at 75% of the resistive load bank KW rating.

FEATURES

  • Used to test diesel generator sets, UPS systems, and other AC power sources that require testing at less than 1.0 power factor
  • Intended to be used in conjunction with a resistive load bank to test a generator or power source at 0.8 power factor (lagging)
  • To achieve a 0.8 power factor, the reactive load bank should be sized at 75% of the resistive load bank KW rating
  • Connected and operated in parallel with the resistive load bank
  • Heavy-gauge steel enclosure
  • Designed for indoor or outdoor installation
  • Equipped with inlet screens between structural members in bottom of unit
  • Removable aluminized steel panels for interior access
  • Channels provided in base structure facilitate handling by fork lift truck from all four directions
  • Single and 3-phase iron core reactors designed for 130°C rise in 50°C environment with maximum of 5% waveform distortion and 0.05 power factor
  • Cooling fan aids convection cooled reactors
  • Cooling fan requires external power source of 120 volts, single phase, 60 hertz
  • Each load step fused using UL class T fuses with 200,000 AIC rating
  • Each 3-phase reactor contains a normally closed thermal switch in each coil
  • Enclosure equipped with thermal switches
  • All thermal switches interconnected with load application control circuit
  • Designed for continuous operation